485848001__Y (waveform)

ERBESSD / 485848001 · sensor attached · replace sensor · analysis runs

Priority

low (score 0.00, higher is worse), calculated 2026-09-07 23:43:22+0000 by analysis 87d7acf80149adbf2da76e8ad2955442.

LevelScoreCalculatedAnalysis
low 0.00 2026-09-07 23:43:22+0000 87d7acf80149adbf2da76e8ad2955442
low 0.00 2026-09-07 23:42:25+0000 3548009e0907be4d4732f98364ae28e5

Latest KPI values (GET /mpoints-streams/{id}/kpi)

30 measurements; latest 2026-09-04 05:40.

KPILatest valuePoints in trend
rms0.381226170087847430
velocity_rms_10_1000hz1.36153916071829630
velocity_rms_2_1000hz1.899163862578477730
velocity_rms_2_max1.90589162061758130
velocity_rms_10_max1.370907866629186730
peak0.796116222665013430
peak2peak1.589646758638158630
crest_factor2.088304227596865330
kurtosis2.022571625989324530
envelope_rms0.2063756435902605630
envelope_peak_score0.081092785449872330

Diagnostic findings (GET /sva/87d7acf80149adbf2da76e8ad2955442/symptoms and /changes/active)

SymptomActiveDetectionsPossible faults
symptomModulation yes 30 active of 30 innerRaceBearingDamage (50%), electricalInterference (30%), beating (20%)

Trend scalars at this measuring point (GET /scalars/?sensor_id=…)

Scalars are keyed by sensor, not by stream — the link to this measuring point is derived: this point's streams name their active sources, the sources name their sensors, and the sensors' scalars are what you see here. The scalars page draws the whole chain.

The sensors at this measuring point report no trend scalars.

rpm: outside 600–3600 RPM an rpm scalar is required — without it, bearing analysis silently returns nothing.

Embedded analysis view

This iframe is the one thing the browser loads straight from the deployment. Its URL carries only the stream id — no credential — and this page's own Content-Security-Policy: frame-src header is what allows the frame (the deployment sets no framing restriction of its own).